Strong Points
Function
The EMergency CPSS range (Emergency Central Power Supply System) has been designed to answer your needs in terms of power supply for your safety system.
All our EMergency products are compliant with standard EN 50171.
Conformity to standards
EN 50171
IEC/EN 62040-1, IEC/EN 62040-2
CE
Advantages
A complete solution for your emergency systems
The EMergency CPSS products are intended to ensure energy supply to emergency escape lighting in the event of mains supply failure.
Depending on the local legislation, it may be suitable for energizing other essential safety equipment, such as:
- electric circuits of automatic fire extinguishing installations,
- paging systems and signaling safety installations,
- smoke extraction equipment,
- carbon monoxide warning systems,
- special safety installations related to specific buildings, e.g. high-risk areas.
The wide range is suitable for all standard needs. For non-standard requests, our team of experts is on hand to adapt the products to your needs.
Technical data
Sn [kVA] | 160 | 200 |
Pn [kW] | 144 | 180 |
Pn according to EN 50171 [kW] | 120 | 150 |
Input / output | 3/3 |
Input | ||
---|---|---|
Model | 160 | 200 |
Rated voltage | 400V 3ph | |
Voltage tolerance(1) | 240V to 480V(1) | |
Rated frequency | 50/60Hz | |
Frequency tolerance | ±10% | |
Power factor/THDI | 0.99/<3% |
Output | ||
---|---|---|
Model | 160 | 200 |
Rated voltage | 400V | |
Voltage tolerance | static load ±1% dynamic load in accordance with VFI-SS-111 | |
Rated frequency | 50/60Hz | |
Frequency tolerance | ±2% (configurable from 1% to 8%) | |
Overload UPS designed @ Pn | 110% for 10 min, 135% for 1 min | |
Crest factor | 3:1 |
UPS Cabinet | |||||||||||
---|---|---|---|---|---|---|---|---|---|---|---|
Model | 160 | 200 | |||||||||
Dimensions W x D x H (mm) | 700 x 800 x 1930 | ||||||||||
Maximum weight (without battery) (kg) | 480 | 500 | |||||||||
Protection degree | IP20 (EN 50171) | ||||||||||
Acoustic level at 1m (ISO 3756) | <68dBA |
Battery | |||||||||||
---|---|---|---|---|---|---|---|---|---|---|---|
Model | 160 | 200 | |||||||||
Type | VRLA with 10-year life expectancy | ||||||||||
Standard back-up time at the end of battery life | 60/90/120min(1) | ||||||||||
Charging capabillity | 80% of back-up time in 12h | ||||||||||
Embedded battery Max BUT(1) | External battery |
Standards | ||
---|---|---|
Model | 160 | 200 |
CPSS | EN 50171 | |
Safety | IEC/EN 62040-1 | |
EMC | IEC/EN 62040-2 | |
Performance | IEC/EN 62040-3 | |
Product declaration | CE |
System
Electrical options
- Transformer embedded in the UPS enclosure.
- Connection to downstream IT earthing system.
- Eco mode to reach up to 98% efficiency.
- Other types of battery available.
Communication
Standard communication features
- User-friendly 7” touch-screen multilingual colour graphic display.
- Slots for communication options.
- Dry-contact interface (configurable voltage-free contacts).
Communication options
- Dry-contact interface (configurable voltage-free contacts).
- MODBUS RTU RS485 or MODBUS TCP.
- NET VISION: professional WEB/SNMP
- Ethernet interface for secure UPS monitoring and remote automatic shutdown.
- REMOTE VIEW PRO supervision software.