Function

The EMergency CPSS range (Emergency Central Power Supply System) has been designed to answer your needs in terms of power supply for your safety system. All our Emergency products are compliant with standard EN 50171.

Conformity to standards

EN 50171

ui/Thin/mkt-prime
Prime
Trustworthy power

Reliable and cost effective protection to assure operational continuity.

Image
Elite UPS logo
ELITE UPS label: a mark of efficiency
Socomec signs up to JRC Code of Conduct for Elite level UPS efficiency that’s fit for the future

Advantages

EN 50171 compliant

- IP20 enclosure compliant with EN 60598-1.
- Fast battery charge: 80% in 12 hours.
- Battery protection against damage due to a polarity inversion.
- Battery protection against deep discharge.
- Long-life battery with 10-year life expectancy (only for 6 kVA).
- Designed to withstand 120% of the nominal charge during the entire back-up period.

Robust with high availability

- True online double conversion technology (VFI) assures high availability and total load protection in any environmental conditions.
- Reliable solution in a wide operating ambient temperature up to 45°C.
- Standard Over Voltage Control Device (OVCD) protects the UPS and the load from dangerous mains peak-voltages.

Flexible autonomy

- Modular battery extension flexibility enables limitless autonomy configuration.
- Hot-swap modular battery extension increases back-up - even after installation - according to the load criticality to be supplied.
- UPS with powerful battery charger for modular battery extension to:
• ensure constant and reliable operation using external high capacity batteries,
• provide power supply continuity during long outages,
• ensure a fast recharging.

Easy and error-free installation

- Quick and simple installation: no configuration necessary on first startup.
- Compact tower UPS system saves space in the operating environment.
- Installation according to the load criticality to be supplied.

Applications

  • Building - Power availability for life safety

Technical data

Model ITY3-EM020LB-K ITY3-EM060LB-K
Sn (kVA) 2 6
Pn (kW) 2 6
Pn according to EN 50171 (kW) 1,5 5
Inverter max withstand power EN 50171 (kW) 2 6
Input / output 1/1
Input
Model ITY3-EM020LB-K ITY3-EM060LB-K
Rated voltage 230V (1ph+N)
Voltage tolerance 160V to 300V 160V to 276V
Rated frequency 50/60Hz
Frequency tolerance ± 2%
Power factor / THDI >0,98% / <5% >0,99
Output
Model ITY3-EM020LB-K ITY3-EM060LB-K
Rated voltage 220/230/240V
Voltage tolerance ±1%
Rated frequency 50/60Hz
Frequency tolerance ± 0,1%
Overload UPS designed @ Pn 110% for 5 min. 130% for 5 sec
Crest factor 3:1
UPS Cabinet
Model ITY3-EM020LB-K ITY3-EM060LB-K
Dimensions L x P x H (mm) 192 x 428 x 322 225 x 416 x 354
Weight (kg) 11 13,5
Protection degree IP20 (EN 50171)
Acoustic level (dBA) 1m (ISO 3756) < 52
Battery
Model ITY3-EM020LB-K ITY3-EM060LB-K
Type VRLA with 5-year life expectancy VRLA with 10-year life expectancy
Charging capability 80% of back-up time in 12h
Standards
Model ITY3-EM020LB-K ITY3-EM060LB-K
CPSS EN 50171
Safety EN 62040-1
EMC EN 62040-2
Performance EN 62040-3
Product certification CE

 

Communication

Standard communication features

- 1 slot for communication options.
- Dry-contact card according to EN 50171.
- USB port for UPS management based on HID protocol.
- MODBUS RTU (RS232).
- LOCAL VIEW software for local UPS monitoring and shutdown for Windows, Linux and MAC OSX.
- Clear and uncluttered LCD interface for easy UPS monitoring, even for less specialist users.

Communication options

- NET VISION: professional WEB/SNMP Ethernet interface for secure UPS monitoring and remote automatic shutdown.
- Environmental Monitoring Device (EMD).
- REMOTE VIEW PRO supervision software.

Assistance

331F85EE-06C9-4809-9910-162B465D771A Created with sketchtool.

Looking for product documentation?

Access product catalogues, operating instructions, technical documents, CAD files,  and more.

F3AF315C-0799-42F2-AF18-B1B77756CAE4 Created with sketchtool.

Questions? We can help!

Contact our technical support.