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

Technical Characteristics

Height [mm] 135
Width [mm] 251
Depth [mm] 218
Weight [kg] 3.83
Control operator Manual Direct : J2 / External : S2
Number of poles 4
Rated current [A] 200
Type Manual I-0-II
Frame size B3

Classification

UNSPSC 39122205
ETIM Class EC000216
IGCC 5177

Commerce

Description Manually Operated Transfer Switch SIRCOVER, switching type I-0-II, frame B3, 4P 200A, direct operation with handle type J2 or external operation with handle type S2. Delivered without handle
Effective date 2013-02-28
Offer Life Cycle Code 40
Country of origin TN

Environmental Sustainability

Climate change - Total - Cradle to Grave [kg CO₂ eq.] 87
Climate change - Total - Cradle to Gate [kg CO₂ eq.] 30
SVHC > 0.1 mass percentage? No
RoHS applicable? Yes

ETIM - Electrical characteristics

Max. rated operation voltage Ue AC [V] 800
Rated operating voltage [V] 400..690
Rated permanent current Iu [A] 200
Rated permanent current at AC-23, 400 V [A] 200
Rated permanent current at AC-21, 400 V [A] 200
Rated short-time withstand current lcw [kA] 7
Rated operation power at AC-23, 400 V [kW] 100
Switching power at 400 V [kW] 100
Conditioned rated short-circuit current Iq [kA] 50
Number of poles 4

ETIM - Mechanical characteristics

Suitable for floor mounting No
Suitable for front mounting 4-hole No
Suitable for front mounting centre No
Suitable for distribution board installation No
Suitable for intermediate mounting Yes
Colour control element Black
Degree of protection (IP), front side IP20
Width [mm] 251
Height [mm] 135
Depth [mm] 218

ETIM - Technical features

Version as main switch Yes
Version as maintenance-/service switch Yes
Version as safety switch Yes
Version as emergency stop installation No
Version as reversing switch Yes
Number of switches 2
Motor drive optional No
Motor drive integrated No
Voltage release optional No
Device construction Built-in device fixed built-in technique
Type of control element Door coupling rotary drive
Interlockable Yes
Type of electrical connection of main circuit Bolt connection

Logistics

GTIN/EAN 3596032736958
Customs number 8536508000
Price unit PC
Weight of the packing unit [kg] 3.83
Length of the packing unit [m] 0.275
Width of the packing unit [m] 0.215
Depth of the packing unit [m] 0.17

Norms

Conformity to standards IEC
  • PDF
    SIRCOVER AC 125~200A_CB Certificate
    Select
  • PDF
    SIRCOVER - Implementation of standard IEC _ EN 61439
    Select
  • PDF
    Manual Transfer Switches
    Select
  • PDF
    SIRCOVER I-0-II
    Select
  • PDF
    SIRCOVER AC 800~1250A_CB Certificate
    Select
  • PDF
    SIRCOVER AC 2000~3200A_CB Certificate
    Select
  • PDF
    SIRCOVER AC 250~400A_CB Certificate
    Select
  • PDF
    SIRCOVER - Manual Transfer Switching Equipment
    Select
  • PDF
    SIRCOVER/ATyS_BUREAU VERITAS certificate
    Select
  • PDF
    SIRCOVER range_UK declaration
    Select
  • PDF
    SIRCOVER & SIRCOVER ByPass_UE declaration
    Select
  • PDF
    SIRCOVER 125-200A_CCC certificate
    Select
  • PDF
    Transfer Switching Equipment - by Socomec
    Select

References

SIRCOVER I-0-II is also available in 29 versions

Item Rated current [A] Number of poles Frame size Control operator Type Select
41AC3013 125 3 B3 Manual Direct : J2 / External : S2 Manual I-0-II
41AC4013 125 4 B3 Manual Direct : J2 / External : S2 Manual I-0-II
41AC3016 160 3 B3 Manual Direct : J2 / External : S2 Manual I-0-II
41AC4016 160 4 B3 Manual Direct : J2 / External : S2 Manual I-0-II
41AC3020 200 3 B3 Manual Direct : J2 / External : S2 Manual I-0-II
41AC3025 250 3 B4 Manual Direct : J2 / External : S2 Manual I-0-II
41AC4025 250 4 B4 Manual Direct : J2 / External : S2 Manual I-0-II
41AC3031 315 3 B4 Manual Direct : J2 / External : S2 Manual I-0-II
41AC4031 315 4 B4 Manual Direct : J2 / External : S2 Manual I-0-II
41AC3040 400 3 B4 Manual Direct : J2 / External : S2 Manual I-0-II
41AC4040 400 4 B4 Manual Direct : J2 / External : S2 Manual I-0-II
41AC3050 500 3 B5 Manual Direct : J2 / External : S2 Manual I-0-II
41AC4050 500 4 B5 Manual Direct : J2 / External : S2 Manual I-0-II
41AC3063 630 3 B5 Manual Direct : J2 / External : S2 Manual I-0-II
41AC4063 630 4 B5 Manual Direct : J2 / External : S2 Manual I-0-II
41AC3080 800 3 B6 Manual Direct : J3 / External : S4 Manual I-0-II
41AC4080 800 4 B6 Manual Direct : J3 / External : S4 Manual I-0-II
41AC3100 1000 3 B6 Manual Direct : J3 / External : S4 Manual I-0-II
41AC4100 1000 4 B6 Manual Direct : J3 / External : S4 Manual I-0-II
41AC3120 1250 3 B6 Manual Direct : J3 / External : S4 Manual I-0-II
41AC4120 1250 4 B6 Manual Direct : J3 / External : S4 Manual I-0-II
41AC3160 1600 3 B7 Manual Direct : J3 / External : S4 Manual I-0-II
41AC4160 1600 4 B7 Manual Direct : J3 / External : S4 Manual I-0-II
41AC3200 2000 3 B8 Manual External : S5 Manual I-0-II
41AC4200 2000 4 B8 Manual External : S5 Manual I-0-II
41AC3250 2500 3 B8 Manual External : S5 Manual I-0-II
41AC4250 2500 4 B8 Manual External : S5 Manual I-0-II
41AC3320 3200 3 B8 Manual External : S5 Manual I-0-II
41AC4320 3200 4 B8 Manual External : S5 Manual I-0-II