Strong Points
Function
The NETYS PR is the ideal solution for protecting small servers, networking devices and peripherals.
Conformity to standards
IEC/EN 62040-1, IEC/EN 62040-2
AS 62040.1.1, AS 62040.1.2, AS 62040.2
CE
RCM (E2376)
Prime
Trustworthy power
Reliable and cost effective protection to assure operational continuity.
Advantages
A secure and professional supply continuity
- Assures service continuity to critical applications.
- Designed for professional applications: the sinevawe inverter technology assures full compatibility with any kind of load and power supply.
Tailored to IT networking
The space and time-saving tower/rack conversion option means it can be installed easily either in tower mode or inside standard 19" rack cabinets depending on the user’s needs.
Simple to install
- No configuration needed on first startup.
- Compact footprint (2U/89 mm) for installation in rack cabinets.
- Attractive design for visible installation in offices.
- USB port and HID protocol as standard for direct interfacing with Windows® systems, without the need for additional specialist software.
Protection for your data line
Integrated NTP protection for LAN/ADSL connection against the risk of data line overvoltage.
Meets practical needs
- Optional battery extension modules (EBM) to meet all back-up time requirements, even after installation.
- Clear and uncluttered LCD interface, with buzzers that immediately indicate the operating status of the UPS, even for less specialist users.
- Simplified maintenance and Battery ‘hot swap’, without closing down other applications.
Easy to use and to integrate
- Wide range of communication protocols available in options (including JBUS, TCP/IP and SNMP) for integration into LAN networks or building management systems (BMS).
- Easy connections to the applications (depending on power) via 8 or 8+1 IEC 320 (IT standard) sockets.
- Load segmentation function to prioritize loads and manage critical situations.
- EPO (Emergency Power Off) emergency stop.
- RS232 advanced connections for the management of the power supply and local/ remote shutdown of applications.
Applications
- Building - Power availability for IT infrastructure
Technical data
Sn | 1700VA | 2200VA | 3300VA |
Pn | 1350W | 1800W | 2700W |
Input/output | 1/1 |
Input | |||
---|---|---|---|
Model | 1700VA | 2200VA | 3300VA |
Rated voltage | 230V | ||
Voltage tolerances | 161V ±4% (selecting wide mode) - 276V ±4% | ||
Rated frequency | 50/60Hz with automatic selection | ||
Mains connection | IEC 320-C14 (10A) | IEC 320-C20 (16A) |
Output | |||
---|---|---|---|
Model | 1700VA | 2200VA | 3300VA |
Automatic Voltage Regulation (AVR) | The AVR increases (boost 1) the output voltage by 14% when the input voltage drops below 90% of the nominal value. The AVR decreases (bucks) the output voltage by 12% when the input voltage rises above 106% of the nominal value. |
||
Rated voltage | 230V ±5% | ||
Rated frequency | 50/60Hz ±0.1% | ||
Power factor | 0.9 @ 1500VA | 0.9 @ 2000VA | 0.9 @ 3000VA |
Wave form | Sine wave | ||
Protection | Normal Mode: overload (110% for 3 minutes) Battery Mode: overload (110% for 30 seconds); shortcircuit protected |
||
Sockets | 8 (10A) x IEC 320 | 8 (10A) x IEC 320 1 (16A) x IEC 320 |
Batteries | |||
---|---|---|---|
Model | 1700VA | 2200VA | 3300VA |
Type | Sealed lead-acid maintenance free - expected life 3/5 years | ||
Back-up time (min)(1) | 6 | 8 | 6 |
Communication | |||
---|---|---|---|
Model | 1700VA | 2200VA | 3300VA |
Interface | RS232 - USB | ||
Ethernet adapter | NET VISION (TCP/IP & SNMP) optional card | ||
Local communication software | Local View | ||
Data line protection | NTP data line suppressor: RJ45 10 Base T |
UPS Cabinet | |||
---|---|---|---|
Model | 1700VA | 2200VA | 3300VA |
Dimensions W x D x H (mm) | 440 x 436 x 87 | 440 x 608 x 87 | |
Weight (kg) | 18 | 28.2 | 31.5 |
Standards | |||
---|---|---|---|
Model | 1700VA | 2200VA | 3300VA |
Safety | IEC/EN 62040-1, AS 62040.1.1, AS 62040.1.2 | ||
EMC | IEC/EN 62040-2, AS 62040.2 | ||
Product declaration | CE, RCM (E2376) |
(1) @ 75% of load.
Communication
Standard communication features
- 1 slot for communication options.
- USB port for UPS management based on HID protocol.
- MODBUS RTU (RS232).
- LOCAL VIEW software for local UPS monitoring and shutdown for Windows, Linux and MAC Osx.
Communication options
- Dry-contact interface.
- NET VISION: professional WEB/SNMP Ethernet interface for secure UPS monitoring and remote automatic shutdown.
- Environmental Monitoring Device (EMD).
- REMOTE VIEW PRO supervision software.
- Rails.
Associated services
With 400 experts and 250 engineers, Socomec offers comprehensive support to optimise the performance and longevity of your equipment
Commissioning
Socomec ensures optimal commissioning of your installations, with inspection, certification and expert support, in person or remotely
Maintenance
Benefit from Socomec experts available on-site and remotely to guarantee the longevity and optimum performance of your installations