Function

Static Transfer Systems (STS) are intelligent switches providing increased supply availability, automatically transferring loads to alternative power sources when the primary power source fails or is not available. They enable flexible site maintenance ensuring high availability.

Conformity to standards

IEC 62310
IEC 60529
AS 62310
AS 60529
IEC 62310-2
AS 62310.2
CE
RCM

ui/Thin/mkt-ultimate
Ultimate
Fault-tolerant power without compromise

Fully redundant architecture for maximum availability, minimum MTTR and risk free maintenance.

Advantages

Standard features

- A smart and flexible transfer system that can be configured according to the type of load.
- Synchronised and non-synchronised sources compatibility (configurable synchronisation tolerance and switching management).
- Fuse-free or fuse-protected design.
- Output fault current sensing.
- Internal CAN Bus.
- Double maintenance bypass.
- Neutral oversizing for non-linear loads compatibility.
- Embedded Inputs, output and maintenance bypass switches (cabinet version).

Alimentation

Supplied by two independent alternate sources, STATYS increases the overall electrical infrasrtucture availability during abnormal events and programmed maintenance.
- Provides redundant power supply to mission critical loads to increase global uptime of the supplied system.
- Increases the power supply availability by choosing the best power supply quality.
- Provides plant segmentation and prevents fault propagation.
- Allows easy extension and easy infrastructure design, ensuring high availability of the power supply to critical applications.
- Facilitates and secures the maintenance or the modifications of the overall electrical installation (source, distribution, switchboard) while the load is kept supplied.

Flexibility

STATYS is available in:
- 2 wires and 2 poles switching, to be connected between phase/neutral or phase/phase.
- 3 wires arrangement without neutral for reduced cable costs and for local zoning of the applications by using insulating transformers,
- 4 wires three-phase arrangement with neutral, with or without neutral pole switching.
STATYS offers:
- Flexible digital control capacity that can adapt to any operational or electrical environment conditions.
- Capability to manage synchronised and non-synchronised sources according to load specificity.

ATSM fonction

Advanced Transformer Switching Management (ATSM). If the upstream network has no distributed neutral cable, two upstream transformers or one downstream transformer can be added to create a neutral reference point at the output. For the downstream solution, STATYS, thanks to ATSM, correctly manages the switching to limit inrush current and avoid the risk of spurious breakers.

Protection

STATYS also provides protection against:
- Main power source outage.
- Failures in the upstream power distribution system.
- Failures caused by faulty equipment supplied by the same source.
- Operator errors.

Applications

  • Data center - Power availability for servers

Technical data

STATYS Cabinet

 

Electrical specifications
Model 200 300 400 600 800 1000 1250 1400 1600
Voltage 208-220/380-415/440V (±10%)
Number of phases 3ph+N or 3ph (+ PE)
Frequency  50Hz or 60Hz (±5Hz (configurable))
Number of poles switching 3 or 4-pole switching
Neutral system Compatible with all earthing systems
Maintenance bypass Interlocked and secured
Overload 150% for 2 minutes - 110% for 60 minutes
Efficiency 99%
Admissible power factor No restrictions

 

Environment
Model 200 300 400 600 800 1000 1250 1400 1600
Operating ambient temperature 0-40°C
Relative humidity 95%
Maximum altitude 1000m a.s.l. without derating
Cooling Forced ventilation
Sound pressure level <60dBA <84dBA

 

Mechanical specifications
Model 200 300 400 600 800 1000 1250 1400 1600
Dimensions W x D x H (1) (mm) 500 x 600 x 1930 700 x 600 x 1930 900 x 600 x 1930 1400 x 950 x 1930 2010 x 815 x 1955
Weight (kg) 195 270 345 685 1200
Degree of protection IP20

 

Standards
Model 200 300 400 600 800 1000 1250 1400 1600
Performance and safety IEC 62310, IEC 60529, AS 62310, AS 60529
EMC C2 category (IEC 62310-2, AS 62310.2)
Protection class CB or PC class
Product declaration CE, RCM (E2376)

 

(1) Depth does not include handles (+40mm).

STATYS Integrable Chassis (OEM)

 

Electrical specifications
Model 200 300 400 600 800 1000 1250 1400 1600 1800
Voltage 208-220/380-415/440V (±10%)
Number of phases 3ph+N or 3ph (+ PE)
Frequency  50Hz or 60Hz (configurable ±5%)
Number of poles switching 3 or 4-pole switching
Neutral system Compatible with all earthing systems
Maintenance bypass Interlocked and secured
Overload 150% for 2 minutes - 110% for 60 minutes
Efficiency 99%
Admissible power factor No restrictions

 

Environment
Model 200 300 400 600 800 1000 1250 1400 1600 1800
Operating ambient temperature 0-40°C
Relative humidity 95%
Maximum altitude 1000m a.s.l. without derating
Cooling Forced ventilation
Acoustic level at 1m (ISO 3746) <60dBA

 

Mechanical specifications
Model 200 300 400 600 800 1000 1250 1400 1600 1800
Dimensions W x D x H (1) (mm) 400 x 586 x 765 600 x 586 x 765 800 x 586 x 765 1000 x 950 x 1930 910 x 815 x 1955
Weight (kg) 70 105 130 495 750
Degree of protection IP20

 

Standards
Model 200 300 400 600 800 1000 1250 1400 1600 1800
Performance and safety IEC 62310, IEC 60529, AS 62310, AS 60529
EMC C2 category (IEC 62310-2, AS 62310.2)
Protection class CB or PC class
Product declaration CE, RCM (E2376)

 

(1) Depth does not include handles (+40mm).

STATYS Hot-Swappable

 

Electrical specifications
Model 32 63 63 100
Voltage  120-127/220-240/254V (±10%) 208-220/380-415/440V (±10%)
Number of phases ph+N or ph-ph (+ PE) 3ph+N or 3ph (+ PE)
Frequency  50Hz or 60Hz (configurable ±5%)
Number of poles switching 2-pole switching 3 or 4-pole switching
Neutral system Compatible with all earthing systems
Maintenance bypass Interlocked and secured
Overload 150% for 2 minutes - 110% for 60 minutes

 

Efficiency
Model 32 63 63 100
Admissible power factor No restrictions

 

Environment
Model 32 63 63 100
Operating ambient temperature 0-40°C
Relative humidity 95%
Maximum altitude  1000m a.s.l. without derating
Cooling Forced ventilation
Acoustic level at 1m (ISO 3746) <45dBA <60dBA

 

Mechanical specifications
Model 32 63 63 100
Dimensions W x D x H(1) (mm) 483 x 747 x 89 (19” x 747 x 2U) 483 x 648 x 400 (19” x 648 x 9U)
Weight (kg) 26 58
Degree of protection IP30

 

Standards
Model 32 63 63 100
Performance and safety IEC 62310, IEC 60529, AS 62310, AS 60529
EMC C2 category (IEC 62310-2, AS 62310.2)
Protection class CB or PC class
Product declaration CE, RCM (E2376)

 

(1) Depth does not include handles (+40mm).

 

Communication

Standard communication features

- LCD or user-friendly 7" touch-screen multilingual graphic colour display.
- Slots for communication options.
- Dry-contact interface (configurable voltage-free contacts).
- Ethernet interface for STS monitoring via WEB pages.
- MODBUS TCP.
- Full digital configuration and setting.

Communication options

- Dry-contact interface (configurable voltage-free contacts).
- MODBUS RTU RS485.
- PROFIBUS / PROFINET gateway.
- REMOTE VIEW PRO supervision software.

Resources

Assistance

331F85EE-06C9-4809-9910-162B465D771A Created with sketchtool.

Looking for product documentation?

Access product catalogues, operating instructions, technical documents, CAD files,  and more.

F3AF315C-0799-42F2-AF18-B1B77756CAE4 Created with sketchtool.

Questions? We can help!

Contact our technical support.