Function

DELPHYS BC is the complete cost-effective solution for the protection of business critical applications.

Conformity to standards

IEC/EN 62040-1, AS 62040.1.1, AS 62040.1.2
EMC IEC/EN 62040-2, AS 62040.2
IEC/EN 62040-3, AS 62040.3
CE, RCM (E2376)

ui/Thin/mkt-prime
Prime
Trustworthy power

Reliable and cost effective protection to assure operational continuity.

Image
Elite UPS logo
ELITE UPS label: a mark of efficiency
Socomec signs up to JRC Code of Conduct for Elite level UPS efficiency that’s fit for the future

Advantages

A complete, cost-effective solution

- Online double conversion mode with an output power factor of 0.9 providing 12 % more active power compare to UPS with a power factor of 0.8.
- Dual input mains allows you to manage independent power sources.
- Increased system availability placing two UPS in parallel for 1+1 redundancy.
- Internal manual bypass for easy maintenance without power interruption (1+1 configuration).
- Multilanguage display

Tailored to your environment

- Saves space with a reduced footprint and optimized cabinet size.
- Low noise level.
- Compact, lightweight and easy to install.
- No neutral required on rectifier input.
- Two-wire battery connection (only +/-).
- Extended battery life and performance with exclusive EBS battery charging management for increased battery life.

Applications

  • Data center - Power availability for precision cooling

Technical data

Sn [kVA] 200 300
Pn [kW] 180 270
Parallel configuration up to 6 units

 

Input
Model 200 300
Rated voltage 400V 3ph
Voltage tolerances 240V to 480V(1)
Rated frequency  50/60Hz ±10%
Power factor/THDI 0.99/< 3%

 

Output
Model 200 300
Rated voltage 400V
Voltage tolerance  static load ±1% dynamic load in accordance with VFI-SS-111
Rated frequency 50/60Hz
Frequency tolerance ±2% (configurable from 1% to 8%) 
Crest factor 3:1

 

Bypass
Model 200 300
Rated voltage rated output voltage
Voltage tolerance ±15% (configurable from 10% to 20%)
Rated frequency 50/60Hz
Frequency tolerance ±2% (configurable for Genset compatibility)

 

Efficiency
Model 200 300
Online mode @ 100% of load up to 94%

 

Environment
Model 200 300
Operating ambient temperature from 0°C up to +40°C(1)
(from 15°C to 25°C for maximum battery life)
Relative humidity 0% - 95% without condensation
Maximum altitude 1000m without derating (max. 3000m)
Acoustic level at 1m (ISO 3746) <68dBA <71dBA

 

UPS cabinet
Model 200 300
Dimensions W x D x H (mm) 700 x 800 x 1930 1000 x 950 x 1930
Weight (kg) 500 830
Degree of protection IP20
Colours RAL 7012, silver grey frontal door

 

Standards
Model 200 300
Safety IEC/EN 62040-1, AS 62040.1.1, AS 62040.1.2
Performance IEC/EN 62040-2, AS 62040.2
EMC IEC/EN 62040-3, AS 62040.3
Product declaration CE, RCM (E2376)

 

(1) Conditions apply.

System

Electrical options

- External battery cabinet.
- External temperature sensor.
- Additional battery chargers.
- Shared battery.
- Galvanic isolation transformer.
- Parallel kit.
- ACS synchronization system.

Communication

Standard communication features

- User-friendly 7” touch-screen multilingual colour graphic display.
- 2 slots for communication options.
- USB port to download UPS report and log file.

Communication options

- Dry-contact interface. (configurable voltage-free contacts).
- MODBUS RTU RS485 or MODBUS TCP.
- PROFIBUS / PROFINET gateway.
- BACnet/IP interface.
- NET VISION: professional WEB/SNMP Ethernet interface for secure UPS monitoring and remote automatic shutdown.
- REMOTE VIEW PRO supervision software.
- IoT gateway for Socomec cloud services and SOLIVE UPS mobile app.
- Remote touch-screen panel.
- Additional Com-slot extension.